Requirements for installation of Fire Sprinkler: From NFPA tables according to hazard We get four important notes which used in our design. Maximum spacing between two sprinkler,Minimum spacing between two sprinkler,Maximum spacing between sprinkler and wall,Minimum spacing between sprinkler and wall.
Requirements for installation of Fire Sprinklers
What is the requirements for installation of Fire sprinkler ?
From NFPA tables according to hazard We get four important notes which used in our design:
- Maximum spacing between two sprinkler equal to (4.6 m).
- Minimum spacing between two sprinkler equal to (1.8m)
- Maximum spacing between sprinkler and wall equal to ( Half of the space between two sprinkler )=(4.6/2 = 2.3 m).
- Minimum spacing between sprinkler and wall equal to 10..2 cm.for easy maintenance.
Protection areas per sprinkler and maximum spacing (SSU/SSP)
|
Protection areas per sprinkler and maximum spacing (SSU/SSP)
|
water sprinkler data & distribution
|
water sprinkler data & distribution |
Area of sprinkler operation (ft^2) and Density(gpm/ft^2)
|
Area of sprinkler operation (ft^2) and Density(gpm/ft^2) |
- Area of sprinklers operation =1500 ft^2
- Protection area per sprinkler = 225 ft^2
- Number of working sprinklers = 1500/225 = 6.666 = 7 sprinklers
- Area of sprinklers operation =1500 ft^2
- Protection area per sprinkler =130ft^2
- Number of working sprinklers=1500/130 =12 sprinklers